HONEYWELL UDC 3000 PDF

The Honeywell UDC Universal Digital Controller is a microprocessor-based stand alone controller. It combines the highest degree of functionality and. Find great deals for Honeywell UDC Universal Digital Controller. Shop with confidence on eBay!. There are UDC ‘s at both ends, however as the set point is managed by Lookout, the controllers just provide local control and display the.

Author: Yozshuk Gashicage
Country: Iraq
Language: English (Spanish)
Genre: Medical
Published (Last): 28 June 2017
Pages: 299
PDF File Size: 20.58 Mb
ePub File Size: 17.63 Mb
ISBN: 840-2-96826-199-2
Downloads: 46321
Price: Free* [*Free Regsitration Required]
Uploader: Tauzshura

It’s free, and you can customize the content you view, as well as being able to subscribe to threads and topics, getting new posts delivered honeywlel your email as they appear.

It doesnt limit the controller output as the PID function will wind the output up until saturation if the measured value never reaches the setpoint. Please log in and try again. Since both UDC work to maintain level, there may be conditions where the two work together or against each other to maintain the reservoir level.

Welcome to the Modbus Community, about the world’s leading automation protocol. Perhaps you could order one from Honeywell.

Some tips for better honeywel results By Anonymous on 23 July, – By Chris Jenerick on 14 November, – Put the controller in manual and wind the output up and down while watching the measured value. The ‘Rng1’ error your getting refers to the analogue input UDC’s are twin-loop honeyell though in your application loop 2 is disabled It shows that error when the input range goes above 20ma or below 4ma.

  LUCAS RUIZ DE RIBAYAZ PDF

Honeywell UDC3000 Specification

The bound manual you are looking for is Product E. To exclude a word, precede it with a “-“, as follows: Your use of this site is subject to the terms and conditions set forth under Legal Notices and the Privacy Policy.

Since the two can be connected through Lookout, you may consider implementing a staged control wherein the downstream UDC handles a majority of level changes in the reservoir small deviations in level. By Bill Clemons on 15 July, – 5: Open the gate x amount for x period.

Your subscription request is being processed. So that i can help you to resolve the problem. If you’re not already a member, consider joining. Could this be a span problem? Use double quotes around phrases, as follows: The inlet control is likely configured for reverse operation increaed level decrease output, close gate.

Thanks for the reply. I’ve fiddled around with a few UDCs and being typical Honeywell the book is about as clear and thick as mud. You have clicked on the “?

HONEYWELL UDC SPECIFICATION Pdf Download.

I would verify your getting a good input signal and the full range of gate movement in reponse. This control occurs at two places on the reservoir: By Steve Smoker on 4 October, – 7: The output signal goes to the head gate and adjusts its position to increase or decrease flow into or out of the reservoir.

  LUNA FRIA JEFFERY DEAVER PDF

Note that common words and, that, etc. NandaKumar on 16 July, – 8: By Darren on 15 November, – 4: You have given some good problem definition.

Honeywell UDC – In Stock, We Buy Sell Repair, Price Quote

You must be a Control. Hi Patti The bound manual you are looking for is Product E. I would like a little more clarification on what your measuring and what your controlling – ‘gate position’ is pretty hard to measure unless you have some sort of valve positioner arrangement.

SPHiLim is the parameter that determines how high the setpoint on the controller can be wound up to.

Honeywell UDC 3000 Universal Digital Controller

What I need to identify is the value that drives the output. The lake receives water from a river and releases it to the same down stream. To search the site, enter your search terms in the box labeled “search the site” and hit Enter. Once you verify everything going in and out of the controller as it should I would then start to look at parameters INSIDE the controller.

Try those and reply if its still not working. The UDC should also receive a level signal from the field indicating actual level.